WHB-891 integrated protection device apply to substations or distribution stations of 35kV voltage class and below, the device can be configured flexible according to usage occasion for line protection device, charge protection device, station transformer protection device, capacitor protection device, motor protection device, motor differential protection.
WHB-891 integrated protection device apply to substations or distribution stations of 35kV voltage class and below, the device can be configured flexible according to usage occasion for line protection device, charge protection device, station transformer protection device, capacitor protection device, motor protection device, motor differential protection.
Line protection device apply to protect line and feeder line of 35kV voltage class and under;
Charging protection device apply to protect bus (subsection) of 35kV voltage class and under;
Station transformer protection device apply to protect station transformer, house transformer and grounding transformer of 35kV voltage class and under;
Capacitor protection device apply to protect parallel capacitor installed by substation or distribution substation of 35kV voltage class and under;
Motor protection device apply to protect small and medium asynchronous motor below 2000 kw of 10kV voltage class and under;
Motor differential protection apply to protect huge asynchronous motor above 2000 kw of 10kV voltage class and under.
Function Classification | No. | Function name | Protection object configuration | |||||
Line | Capacitor | Station transformer | Motor | Charge | Motor differential | |||
Protection function | 1 | Three-section overcurrent protection | √ (directional and undervoltage block) |
√ (complex- voltage block) |
√ | √ | √ | √ |
2 | Overcurrent accelerating protection | √ | ||||||
3 | Overload protection | √ | √ | √ | √ | |||
4 | Inverse-time overcurrent protection | √ | √ | √ | √ | √ | ||
5 | Two-section charging protection | √ | ||||||
6 | FC loop blocking protection | √ | √ | √ | ||||
7 | Motor start overtime protection | √ | √ | |||||
8 | Thermal overload protection | √ | √ | |||||
9 | Two-section definite time negative sequence overcurrent protection | √ | √ | √ | ||||
10 | Inverse-time negative sequence overcurrent protection | √ | √ | |||||
11 | Three section zero-sequence overcurrent protection | √ | √ | √ | √ | √ | √ | |
12 | Low voltage side zero sequence overcurrent protection | √ | ||||||
13 | Low voltage side zero sequence inverse-time overcurrent protection | √ | ||||||
14 | Undervoltage load shedding protection | √ | ||||||
15 | Voltage loss protection | √ | ||||||
16 | Under frequency load shedding protection | √ | √ | √ | √ | |||
17 | Undervoltage protection | √ | √ | √ | √ | |||
18 | Overvoltage protection | √ | √ | √ | ||||
19 | Zero-sequence over-voltage protection | √ | ||||||
20 | Unbalanced current protection | √ | ||||||
21 | Unbalanced voltage protection | √ | ||||||
22 | Three-phase one-shot automatic reclosing function | √ | ||||||
23 | Four way non electrical quantity protection | √ | √ | √ | √ | √ | √ | |
24 | Differential quick-break protection | √ | ||||||
25 | Percentage differential protection | √ | ||||||
Auxiliary Function | 1 | Control loop abnormal detection | √ | √ | √ | √ | √ | √ |
2 | Hardcart position abnormal detection | √ | √ | √ | √ | √ | √ | |
3 | spring unstored energy detection | √ | √ | √ | √ | √ | √ | |
3 | Circuit breaker open position abnormal detection | √ | √ | √ | √ | √ | √ | |
5 | Voltage transformer supervision | √ | √ | √ | √ | √ | √ | |
6 | Line voltage transformer supervision | √ | ||||||
7 | Manually tripping access abnormal detection | √ | √ | √ | √ | √ | √ | |
8 | Difference current out-of-limit detection | √ | ||||||
9 | Current transformer supervision | √ | ||||||
Measure and Control Function | 1 | Remote signaling acquisition | √ | √ | √ | √ | √ | √ |
2 | Remote control tripping and closing circuit breaker | √ | √ | √ | √ | √ | √ | |
3 | Analog telemetering acquisition | √ | √ | √ | √ | √ | √ | |
4 | Fault wave records | √ | √ | √ | √ | √ | √ |