WGB-681A generator protection device is a microprocessor-based unit designed to protect large capacity station service transformers, substation service transformers, and grounding transformers in small current or small resistance grounding systems up to 10kV. It can be installed directly in high voltage switch cabinets or within a screen body.
WGB-681A generator protection device (Hereinafter referred to as the device) is a microprocessor-based protection device with advanced and complete functions, mainly applies to protect large capacity station service transformer, substation service transformer and grounding transformer in small current grounding system or small resistance grounding system of 10kV voltage class and under. It can be directly installed in the high voltage switch cabinet or installed in a screen body.
Protective Functions | Abbr | |
1 | Instantaneous differential protection | InstDiff |
2 | Percentage differential protection | PcntDiff |
3 |
Stage 1,stage 2 overcurrent protection with compound voltage blocking(memory) |
OC1, OC2 |
4 | Overload protection | OvLd |
5 | Inverse-time overload protection | InvOvLd |
6 | Three-stage negative sequence overcurrent protection | NegOC1, NegOC2, InvNegOC |
7 | Zero sequence overcurrent protection | ZeroOC |
8 | Overvoltage protection | OV |
9 | Undervoltage protection | UV |
10 | Zero sequence overvoltage protection | ZeroOV |
11 | Difference current out-of-limit protection | Diff_OOL |
12 | Current transformer supervision | CTS |
13 | Reverse-power protection | RevP |
14 | Loss of excitation protection | LossExc |
15 | Rotor one point earth-fault protection | 1PEF_Rot |
16 | Rotor two points earth-fault protection | 2PEF_Rot |
17 | Voltage transformer supervision | VTS |
18 |
Four ways non electrical quantity protection |
Non-E1, Non-E2, Non-E3,
Non-E4 |
19 | Control loop check | Control Loop Chk |
20 | Handcart position check | Handcart Pos Chk |
21 | Circuit breaker open position check | CB Open Pos Chk |
22 | Spring not store energy check | Spring not-E Chk |
Measure and Control Functions | ||
1 |
Remote signaling acquisition, device remote signaling change and fault
remote signaling |
√ |
2 | Remote control tripping and closing circuit breaker | √ |
3 | Analog telemetering: IA, IB, IC, Ua, Ub, Uc, Uab, Ubc, Uca, P, Q, f, Cosf | √ |
4 | Fault wave records | √ |
5 | Three channels 4-20mA direct current output |
Optional |
6 | Four channels 4-20mA direct current input |
Communication Functions | ||
1 |
Two-way RS485 communication interface, support IEC-103, MODBUS-RTU
communication protocols |
√ |
2 |
Two-wayRJ45 Ethernet interface, support TCP-103, IEC-104 communication protocols |
√ |
3 | One-way time synchronization with pulse or B code mode | √ |
4 | Support IEC61850 communication protocol | Optional |
Main features
Device has universal AC-DC auxiliary power supply; the maximum input voltage is 500V, suitable for all kinds of complicated power supply place;
Device has universal AC-DC operation circuit and binary input circuit power supply, which can apply to AC or DC power supply system.