The WGB-601A is a measurement and control device designed for substation automatic systems at 66kV and below. It can also function as a standalone measurement and control unit. The device includes measurement, control, monitoring, and recording features and can be installed directly in a high-voltage switch cabinet or in a panel.

Device introduction

WGB-601A is a measurement and control device designed for substation automatic systems at 66kV and below. It can also function as a standalone measurement and control unit. The device includes measurement, control, monitoring, and recording features and can be installed directly in a high-voltage switch cabinet or in a panel.

Function configuration

MeasureandControlFunctions

 

1

Remote signaling acquisition, device remote signaling change and fault remote signaling

 

2

Four group remote control tripping and closing circuit

breaker, two group remote control regulating voltage

3

Two group analog telemetering: IA, IB, IC, Ua, Ub, Uc,

Uab, Ubc, Uca, P, Q, f, Cosf

4

Three channels 4-20mA direct current output

5

Four channels 4-20mA direct current input

Communication Functions

1

Two-way RS485 communication interface, support IEC-103, MODBUS-RTU communication protocols

2

Two-wayRJ45 Ethernet interface, support TCP-103,

IEC-104 communication protocols

3

One-way time synchronization with pulse or B code mode

4

Support IEC61850 communication protocol

Optional

Main features

  • Thedevice has universal AC/DC Input Power, which has a wide adaptability :

Device has universal AC/DC auxiliary power supply; the maximum input voltage is 500V, suitable for all kinds of complicated power supply place;

Device has universal AC/DC binary input circuit power supply, which can apply to AC or DC power supply system.

  • The device has powerful communication function, standard device configure two Ethernet and two RS485 communication interface and convenient for multiple networking mode, device has flexible communication, which support IEC61850, IEC-103, TCP-103, IEC-104, MODBUS-RTU and other communication protocols, facilitate communication with a variety of convenient networking with various microcomputer monitoring or the protection and management.
  • Thedevice has rigorous time synchronization, which supports network time synchronization, PPS, PPM or B codes and other time synchronization mode
  • Using dual 32-bit high performance embedded microcomputer processor, RAM and flash memory with largecapacity; using SOC solution, which greatly enhanced the capability of data processing , logic operation and information storage and advanced operational speed and reliability.
  • The device uses 16 high precision A/D for data acquisition, collecting 64 points per cycle, which has high measuring accuracy.
  • Back inserted and drawn modules, strong and weak electricity separation; enhanced unit chassis designed for resisting strong vibration and interference, which can be scattered installed on the switch
  • The device can keep more than 400 recent events record and operation record, can keep recording data of 5 times faults occurred recently.
  • Ithas liquid crystal display, English display and menu
  • Real-timemultitasking operating system, modular programming; real-time, high
  • Thereare 8 sets of protection setting value, which are safe and convenient to
  • Deviceis configured with three channels 4-20mA output and four channels 4-20mA input, which is convenient for industrial customers to gather data and extend control functions.
  • Device has rich resource of binary input and binary output, up to 28 channels binary input and 16 channels binary output, standby relay output is not less than 6, base which it is convenient to extend or control signal output.