Products

WGB-871A Microcomputer-Based Integrated Protection Device

WGB-871A Microcomputer-Based Integrated Protection Device

WGB-871A microcomputer-based integrated protection device apply to power distribution and electricity utilization place with voltage levels of 10kV and below. It can be configured flexible according to usage occasion for line protection, station transformer protection, capacitor protection, motor protection and busbar (sectionalized) charging protection.

Application

WGB-871A microcomputer-based integrated protection device apply to power distribution and electricity utilization place with voltage levels of 10kV and below, the device adopts a variety of adaptive technology and all-in-one design concept, which is convenient for engineering selection and field application.

The device can be configured flexible according to usage occasion for line protection, station transformer protection,  capacitor protection, motor protection and busbar (sectionalized) charging protection.

Line protection device apply to protect line and feeder line of 10kV voltage class and under;

Station transformer protection device apply to protect station transformer, house transformer and grounding transformer with voltage levels of 10kV and below;

Capacitor protection device apply to protect parallel capacitor installed by power distribution and electricity utilization place with voltage levels of 10kV and below;

Motor protection device apply to protect small and medium asynchronous motor below 2000 kw with voltage levels of 10kV and below;

Charging protection device apply to protect bus (sectionalized) with voltage levels of 10kV and below.

 


Product Feature

  • The width range of the working power supply is designed and is AC and DC universal.
  • Device adopt an all-in-one design concept, which built in five protection objects to support flexible switching.
  • Integrated chassis design, small volume, small occupation space, suitable for various cabinet installation.
  • Use graphic LCD English display, menu type operation, easy to use.
  • The binary inputs adopt strong electricity design, AC and DC universal, has strong anti-interference ability
  • Using independent high-precision ADC, with high protection accuracy and strong anti-interference ability.
  • Have an independent measurement function, and the power measurement accuracy up to 0.5.
  • Relay exports adopt matrix configuration, which can be programmed on site and easy to use.
  • Operation circuits is AC and DC universal and adapted to multiple operating mechanism.
  • Standard device is configured with RS485 and Ethernet communication interface, supporting multiple communication protocol such as IEC103 and Modbus.
  • 8 sets of protection setting value, and is convenient to switch protection setting zone.
  • Can save 400 recent report records to facilitate traceability analysis of problems.
  • Support the fault recording function, which is convenient for accident analysis.

Function configuration

Protection function NO. Function name Protection object configuration
Line Station transformer Capacitor Motor Charge
1 Three – stage overcurrent protection √ (directional and undervoltage block) √ (complex – voltage block)
2 Overcurrent accelerating protection
3 Overload protection
4 Inverse – time overcurrent protection
5 Two – stage charging protection
6 FC loop blocking protection
7 Motor startup overtime protection
8 Thermal overload protection
9 Two – stage definite time negative sequence overcurrent protection
Protection function NO. Function name Protection object configuration
Line Station transformer Capacitor Motor Charge
10 Inverse-time negative sequence overcurrent protection
11 Stage I zero-sequence overcurrent protection √(High voltage side)
12 Stage II zero-sequence overcurrent protection √(High voltage side)
13 Stage III zero-sequence overcurrent protection √(High voltage side)
14 Low voltage side zero sequence overcurrent protection
15 Low voltage side zero sequence inverse-time overcurrent protection
16 Undervoltage load shedding protection
17 Under frequency load shedding protection
18 Loss voltage protection
19 Undervoltage protection
20 Overvoltage protection
21 Zero-sequence over-voltage protection
22 Unbalanced current protection
23 Unbalanced voltage protection
24 Three-phase one-shot automatic reclosing function
25 Four way non electrical quantity protection