Products

WGB-631A Transformer Protection Device

WGB-631A Transformer Protection Device

WGB-631A transformer protection device (Hereinafter referred to as the device) mainly applies to protect station service transformer, substation service transformer and grounding transformer in small current grounding system or small resistance grounding system of 10kV voltage class and under. It can be directly installed in the high voltage switch cabinet or installed in a screen body.

Device introduction

WGB-631A transformer protection device (Hereinafter referred to as the device) mainly applies to protect station service transformer, substation service transformer and grounding transformer in small current grounding system or small resistance grounding system of 10kV voltage class and under. It can be directly installed in the high voltage switch cabinet or installed in a screen body.

 

Function configuration

Protective Functions Abbr
 

1

Three-stage overcurrent protection with complex voltage blocking  

OC1,OC2,OC3

2 Overload protection OvLd
3 Inverse-time overcurrent protection InvOC
4 Two-stage negative sequence overcurrent protection NegOC1, NegOC2
 

5

Three- stage zero sequence overcurrent protection at the high voltage side  

ZOC1_H, ZOC2_H, ZOC3_H

6 Zero sequence overcurrent protection at the low voltage side ZOC_L
7 Inverse-time zero sequence overcurrent protection at the low voltage side  

InvZOC_L

8 Undervoltage protection En_UV
9 Zero sequence overvoltage protection En_ZeroOV
 

 

10

 

 

Non-electrical quantity protection

Heavy gas, Light gas, Ultra-H temp, High temp, Non-E1, Non-E2, Non-E3, Non-E4
11 FC loop blocking function FC-BLK
12 Voltage transformer supervision function VTS
13 Control loop check Control Loop Chk
14 Circuit breaker open position check CB Open Pos Chk
15 Handcart position check Handcart Pos Chk
16 Spring not store energy check Spring not-E Chk
Measure and Control Functions
 

1

Remote signaling acquisition, device remote signaling change and fault

remote signaling

 

2 Remote control tripping and closing circuit breaker
3 Analog telemetering: IA, IB,IC, Ua, Ub, Uc, Uab, Ubc, Uca, P, Q, f, Cosf
4 Fault wave records
5 Three channels 4-20mA direct current output  

Optional

6 Four channels 4-20mA direct current input
Communication Functions
 

1

Two-way RS485 communication interface, support IEC-103, MODBUS-RTU communication protocols  

 

2

Two-wayRJ45 Ethernet interface, support TCP-103, IEC-104 communication protocols  

3 One-way time synchronization with pulse or B code mode
4 Support IEC61850 communication protocol Optional

Main features

  • Thedevice has universal AC-DC Input Power, which has a wide adaptability :

Device has universal AC-DC auxiliary power supply; the maximum input voltage is 500V, suitable for all kinds of complicated power supply place;

Device has universal AC-DC operation circuit and binary input circuit power supply, which can apply to AC or DC power supply system.

  • The device has powerful communication function, standard device configure two Ethernet and two RS485 communication interface and convenient for multiple networking mode, device has flexible communication, which support IEC61850 (optional), IEC-103, TCP-103, IEC-104, MODBUS-RTUand other communication protocols, facilitate communication with a variety of convenient networking with various microcomputer monitoring or the protection and management.
  • Thedevice has rigorous time synchronization, which supports network time synchronization, PPS, PPM or B codes and other time synchronization mode
  • Using dual 32-bit high performance embedded microcomputer processor, RAM and flash memory with largecapacity; using SOC solution, which greatly enhanced the capability of data processing , logic operation and information storage and advanced operational speed and reliability.
  • The device uses 16 high precision A/D for data acquisition, collecting 64 points per cycle, which has high measuring accuracy.
  • Back inserted and drawn modules, strong and weak electricity separation; enhanced unit chassis designed for resisting strong vibration and interference, which can be scattered installed on the switch
  • The device can keep more than 400 recent events record and operation record, can keep recording data of 5 times faults occurred recently.
  • Ithas liquid crystal display, English display and menu
  • Real-timemultitasking operating system, modular programming; real-time, high
  • Thereare 8 sets of protection setting value, which are safe and convenient to
  • It is optional for device to be configured with three channels 4-20mAoutput and four channels 4-20mA input,which is convenient for industrial customers to gather data and extend control functions.
  • Devicehas rich resource of binary input and Binary output, up to 28 channels Binary input and 16 channels Binary output, standby relay output is not less than 6, base which it is convenient to extend or control signal output.
  • Devicehas complete operation circuit and remote controls of circuit
  • Highintegrated degree: device has protection, measure, control and other