WGB-670A Series backup power automatic switch device (Hereinafter referred to as the device) is fully functional advanced microcomputer-based backup power automatic switch device, mainly apply to automatic switch incoming line switch, section (bridge) switch of 35kV voltage class and under. It can be directly installed in the high voltage switch cabinet or installed in a screen body.
WGB-670A Series backup power automatic switch device (Hereinafter referred to as the device) is fully functional advanced microcomputer-based backup power automatic switch device, mainly apply to automatic switch incoming line switch, section (bridge) switch of 35kV voltage class and under. It can be directly installed in the high voltage switch cabinet or installed in a screen body.
Protective Functions | Abbr | WGB-671A | WGB-672A | |
1 |
Incoming line auto-switching (mode 1,2,5,6) |
Mode 1, Mode 2,
Mode 5, Mode 6 |
√ |
|
2 | Section (bridge) switch auto-switching | Mode 3, Mode 4 | √ | √ |
3 | Auto-switching self-recovery | Self-R | √ | √ |
4 | Incoming line 1 overcurrent accelerating protection | OC_Accel1 | √ | |
5 | Incoming line 2 overcurrent accelerating protection | OC_Accel2 | √ | |
6 | Incoming line 1 overload protection | OvLd_L1 | √ | |
7 | Incoming line 2 overload protection | OvLd_L2 | √ | |
8 | Three-stage overcurrent protection | OC1, OC2, OC3 | √ | |
9 | Overcurrent accelerating protection | OC_Accel | √ | |
10 | Zero-sequence overcurrent protection | ZeroOC | √ | |
11 | Zero-sequence overcurrent accelerating protection | ZOC_Accel | √ | |
12 | Overload cutoff protection | OL_CutOff | √ | |
13 | Bus VT supervision | VTS_B1, VTS_B2 | √ | √ |
14 | Incoming line VT supervision | VTS_L1, VTS_L2 | √ | √ |
15 |
Switch open position check |
CB1 Open Pos Chk, CB2 Open Pos Chk, CB3 Open Pos Chk |
√ |
√ |
16 | Section switch control loop check | Control Loop Chk | √ | |
17 | Section switch handcart position check | Handcart Pos Chk | √ | |
18 | Section switch Spring not store energy check | Spring not-E Chk | √ |
Measure and Control Functions | ||
1 |
Remote signaling acquisition, device remote signaling change and fault
remote signaling |
√ |
2 | Remote control tripping and closing circuit breaker | √ |
3 |
Analog telemetering: (WGB-671A) Ia1,Ib1,Ic1,Ia2,Ib2,Ic2,Ua1,Ub1,Uc1,Ux1,Ua2,Ub2,Uc2,Ux2,Uab1,Ubc1,Uc
a1,Uab2,Ubc2,Uca2 |
√ |
Analog telemetering: (WGB-672A) IA,IB,IC,UA1,UB1,UC1,P,Q,F,COS,Uab1,Ubc1,Uca1,Uab2,Ubc2,Uca2,Ux 1,Ux2,I0+,I0-,U0+,U0- |
√ |
|
4 | Fault wave records | √ |
5 | Three channels 4-20mA direct current output |
Optional |
6 | Four channels 4-20mA direct current input |
Communication Functions | ||
1 |
Two-way RS485 communication interface, support IEC-103, MODBUS-RTU communication protocols |
√ |
2 |
Two-wayRJ45 Ethernet interface, support TCP-103, IEC-104 communication protocols |
√ |
3 | One-way time synchronization with pulse or B code mode | √ |
4 | Support IEC61850 communication protocol | Optional |
Main features
Device has universal AC-DC auxiliary power supply; the maximum input voltage is 500V, suitable for all kinds of complicated power supply place;
Device has universal AC-DC operation circuit and binary input circuit power supply, which can apply to AC or DC power supply system.